Bg

NXSAFE Movable-type indoor AC metal-enclosed switchgear

NXSAFE removable enclosed switchgear is mainly intended for primary distribution system including transformer substation, and also available for switching station and other secondary distribution system, or user terminal power supply system.

  • Hertzman
  • China
  • Information
  • Download

NXSAFE

Movable-type indoor AC metal-enclosed switchgear


Name UnitValue 
Rated voltagekV12
Rated frequency Hz50
Rated currency A≤4000
Rated currency 
1.1Ir
Rated power frequency withstand voltage (1min)kV42

Rated lightning impulse withstand voltage (peak value)

kV75
Rated short-circuit breaking currentkA40
Rated short-circuit close currentkA100
Rated short-time withstand current and duration timekA/s40/4
Rated peak withstand current kA100
Auxiliary and control circuit short-duration power-frequency withstand voltage kV2
Partial discharge

Test voltage

kV1.1×12

Single insulator

pC≤3
Protection gradeHousing
IP4X
Compartment
IP2X
Creepage distance

Porcelain material (to earth)

mm≥216
Organic materials (to the ground)mm≥240

Phase-to-phase and phase-to-earth clearance (air insulation)

Test voltage

mm≥125
Lost running continuity category  

Single insulator

mmLSC2
Minimum clearance between SMC partition (is any) and charged conductorHousing mm≥30
SMC partition thickness Compartmentmm≥5
Cooling method 

Porcelain material (to earth)


Self cooling 1)

Allowable duration of internal arcOrganic materials (to the ground)s≥0.5
Note: 1) Air cooling will be adopted at rated current ≥3150A.